BỘ LƯU ĐIỆN (UPS) ARES ONLINE 2KVA/ 2KW, Tower/ Rackmount, 220V, AR-MP2KSRT, AR-MP2KHRT

    Liên hệ

    Mã hàng: AR-MP2KSRT, AR-MP2KHRT

    Thông tin nhanh về sản phẩm

    AR-MP2KSRT (Internal battery)
    BỘ LƯU ĐIỆN (UPS) ARES ONLINE 2KVA/ 2KW, Tower/ Rackmount, 220V, AR-MP2KSRT

    AR-MP2KHSRT (External battery)
    BỘ LƯU ĐIỆN (UPS) ARES ONLINE 2KVA/ 2KW, Tower/ Rackmount, 220V, AR-MP2KHRT, lắp ắc quy ngoài

    User manual
    for ​AR-MP1KSRT, AR-MP1KHRT/ ​AR-MP2KSRT, AR-MP2KHRT/ ​AR-MP3KSRT, AR-MP3KHRT

     
    THÔNG TIN THAY THẾ ẮC QUY CHO UPS
    (UPS BATTERY REPLACEMENT)
    Tên & số lượng bộ ắc quy lắp trong UPS
    (Internal battery cartridge name
    & quantity)
    BỘ SẠC BÌNH
    (BATTERY CHARGER)
    AR-MP2KSRT (internal battery)
    48VDC / 72VDC/ 1A 
    Output Voltage: 54.7V (±1%) / 82.1V (±1%)
    AR-MP2KHSRT (external battery)
    48VDC / 72VDC / 6A / 12A 
    Output Voltage: 54.7V (±1%) / 82.1V (±1%)
    Bộ ắc quy lắp trong UPS
    (Internal battery pack)
    =48VDC/ 72VDC
    =1x 4/ 6x 12Vx 7Ah ~ 9Ah
    =4/ 6 bình, mắc thành 1 chuỗi 48/ 72VDC.
    Tủ ắc quy lắp ngoài/
    Tủ ắc quy mở rộng
    (External battery cabinet/
    External extended battery cabinet)
    =48VDC hoặc 72VDC
    =1x 4 hoặc 6x 12Vx XXAh
    =4 hoặc 6 bình, mắc thành 1 chuỗi 48 hoặc 72VDC.
    Dung lượng ắc quy (Ah) tùy chọn.
    Thời gian sạc lại
    (Typical recharge time)
    ​8+ hours to 90% after complete discharge
    Ắc quy
    khuyến nghị thay thế cho UPS
    (Recommended replacement
    battery)
    WP7.2-12 WPL7.2-12
    WP7-12(28W WP1236W WP9-12SHR